The requirements for pressure tests are set forth in 49 CFR 180.407(g). All components of the CT wall must be pressure tested. “CT wall” means those parts of the CT that make up the primary lading retention structure, including shell, bulkheads, and fittings and, when closed, yield the minimum volume of the CT assembly.86 As part of the pressure test, the inspector must perform an external and internal visual inspection, except in the case of an MC 338 CT or a CT not equipped with a manhole or inspection opening for which an internal inspection is not required. All self-closing pressure relief valves, including emergency relief vents and normal vents, must be removed from the CT for inspection and testing.
The pressure test includes the following:
- Open each self-closing pressure relief valve that is an emergency relief vent to the required set pressure and seat it to a leak-tight condition at 90 percent of the set-to-discharge pressure or the pressure prescribed for the applicable CT specification.
- Using the testing criteria established by the valve manufacturer, test the normal vents (1 psig vents).
- Replace all self-closing pressure relief devices not tested or failing the pressure tests.
- Except for CTs carrying lading corrosive to the tank, inspect areas covered by the upper coupler (i.e., fifth wheel) assembly for corroded and abraded areas, dents, distortions, defects in weld, and any other condition that might render the tank unsafe. Note: The upper coupler (i.e., fifth wheel) assembly must be removed from the CT for this inspection.
- Hydrostatically or pneumatically test the CT to the internal pressure specified in table 7. At no time during the pressure test may a CT be subject to pressures that exceed those identified in Table 7. 49 CFR 180.407(g)(1)(iv) internal test pressures for CT pressure tests.
When testing multi-tank CTs, the tank must be tested with the adjacent CTs empty and at atmospheric pressure.
All closures except pressure-relief devices must be in place during the test. All prescribed loading and unloading venting devices rated at less than test pressure may be removed during the test. If retained, the devices must be rendered inoperative by clamps, plugs, or other equally effective restraining devices. However, restraining devices may not prevent detection of leaks or damage the venting devices and must be removed immediately after the test is completed.
When testing an insulated CT, the insulation and jacketing does not need to be removed unless it is otherwise impossible to reach test pressure and maintain a condition of pressure equilibrium after test pressure is reached or the vacuum integrity cannot be maintained in the insulation space.
If an MC 338 CT used for the transportation of a flammable gas, oxygen, or refrigerated liquid is opened for any reason, the cleanliness must be verified prior to closure using the procedures contained in §178.338-15.
All pressure-bearing portions of a CT heating system employing a medium such as, but not limited to, steam or hot water for heating the lading must be hydrostatically pressure tested at least once every 5 years. The test pressure must be at least the maximum system design operating pressure and must be maintained for 5 minutes. A heating system employing flues for heating the lading must be tested to ensure against lading leakage into the flues or into the atmosphere. Exceptions are as follows:
- Pressure testing is not required for MC 330 and MC 331 CTs in dedicated sodium metal service.
- Pressure testing is not required for uninsulated lined CTs with a design pressure or MAWP of 15 psig or less, which receive an external visual inspection and a lining inspection at least once a year.
A CT that leaks, fails to retain test pressure or pneumatic inspection pressure, or shows distortion, excessive permanent expansion, or other evidence of weakness that might render the CT unsafe for transportation service may not be returned to service except as follows:
- A CT with a heating system that does not hold pressure may remain in service as an unheated CT if both - The heating system remains in place and is structurally sound and no lading may leak into the heating system - and - The specification plate heating system information is changed to indicate that the CT has no working heating system.
Results of the inspection must be recorded and include any defects discovered and steps taken to remedy the defect.